So my friend had an ex install a subpanel out on a separated deck for a hot tub. They couldn't get the hot tub main board to power on. I come over one day and found the following:
•Subpanel has 2 hot legs and a ground coming in.
•Using 60amp GFCI 220v breaker
•Load Neutral coming from the circuit breaker was connected to Neutral bus bar
•Neutral from hot tub was connected to Neutral bar
•Jumper was placed from Neutral bar to Ground bar..............
Measuring each hot to neutral gave 120v...
220 sub panel with no Neutral
•Subpanel has 2 hot legs and a ground coming in.
•Using 60amp GFCI 220v breaker
•Load Neutral coming from the circuit breaker was connected to Neutral bus bar
•Neutral from hot tub was connected to Neutral bar
•Jumper was placed from Neutral bar to Ground bar..............
Measuring each hot to neutral gave 120v...
220 sub panel with no Neutral